Place in the house · Heat load

What exactly is the heat load?

The heat load is the heat your house loses, and which therefore has to be topped up so that it stays warm inside. You can picture it as a bucket with holes. It is measured in kilowatts.

Picture a bucket with holes. The heat in the house is the water. The walls, the windows and the roof are the holes. The colder it is outside, the faster it runs out. For it to stay at 21 degrees inside, exactly as much heat has to flow in as is lost. That amount is called the heat load.

Every renovation plugs holes. The model house was built in 1967, has around 125 square meters of living space and was barely insulated back then. In the 90s it got new windows, and later the roof was insulated. The facade is still uninsulated today. The bucket loses considerably less today than in 1967, but still not a small amount.

How cold a day do you plan for? For every location in Germany there is a fixed calculation value, the design outdoor temperature. Depending on the region, it is between about minus 10 and minus 16 degrees. A heating system is sized for that day. For the model house it's minus 12 degrees. Which value applies to your location is shown on the climate map of the German Heat Pump Association (Bundesverband Wärmepumpe): waermepumpe.de/normen-technik/klimakarte

The heat losses at minus 12 degrees give the heat load of the model house: a good 11 kilowatts. The important part: there are only a few days like that in a year. On a normal winter day at 2 degrees, the same house needs only about 6 kilowatts, so just over half. Over the whole year, that adds up to around 21,000 kilowatt-hours of heat.

The size of the heat pump should be based on exactly this heat load. If it's too big or too small, it gives away efficiency. In the model house, the heat pump doesn't manage the full 11 kilowatts at minus 12 degrees. Then an electric backup heater kicks in. It turns one kilowatt-hour of electricity into exactly one kilowatt-hour of heat, not three or four.

So the coldest days are the most expensive. On those days the house needs the most heat, and the heat pump works least efficiently. At minus 7 degrees, with a flow temperature of 35 degrees it still delivers just under three times as much heat as the electricity it uses, with 55 degrees only twice as much.

The heat load doesn't tell you yet whether your flow temperature is enough. For that you need to know what the individual radiators can deliver. That's explained in the place called Radiators.

More on this in the video on flow temperature (in German, with translated chapters and transcript).